9th Edition of the Florida Building Code 2026

Several counties have distributed emails stating that the State of Florida will adopt the 9th Edition of the Florida Building Code on December 31, 2026. It is important to note that this adoption will incorporate the 2023 National Electrical Code (NEC), not the 2026 NEC. 

As a follow-up to the AC GFCI protection discussion, when the Florida Building Code (FBC) adopts the 9th Edition, the requirement for GFCI protection on AC compressors will be eliminated. See the excerpt below from the 2026 FBC.

2026 Florida Building Code 2026 Ed.    SECTION E3408— GFCI PROTECTION
E3408.1

NFPA 70-23: National Electrical Code, Article 210 (Branch Circuits), Section 210.8, Ground-Fault Circuit-Interrupter Protection for Personnel, is amended to read as follows:

210.8(F) Outdoor Outlets. For dwellings, all outdoor outlets, other than those covered in 210.8(A), Exception No. 1, including outlets installed in the following locations, and supplied by single-phase branch circuits rated 150 volts or less to ground, 50 amperes or less, shall be provided with GFCI protection:

(1) Garages that have floors located at or below grade level

(2) Accessory buildings

(3) Boathouses

If equipment supplied by an outlet covered under the requirements of this section is replaced, the outlet shall be supplied with GFCI protection.

Exception No. 1: GFCI protection shall not be required on lighting outlets other than those covered in 210.8(C).

Exception No. 2: GFCI protection shall not be required for listed HVAC equipment.


Till next time be safe work safe

Jake


Continue Reading9th Edition of the Florida Building Code 2026

210.52©(2) Island and Peninsular Countertops and Work Surfaces, (3) Receptacle Outlet Location.

Receptacles serving island and peninsular countertops are now optional rather than mandatory, provided a junction box or conduit is installed for future expansion. Outlets mounted under the countertop—such as on the side of a cabinet are no longer permitted. Permissible placements are strictly limited to listed pop-up assemblies installed in the surface or traditional outlets mounted on or up to 20 inches above the countertop.

 image

210.52(C) (2) Island and Peninsular Countertops and Work Surfaces.

Receptacle outlets, if installed to serve an island or peninsular countertop or work surface, shall be installed in accordance with 210.52(C)(3). If a receptacle outlet is not provided to serve an island or peninsular countertop or work surface, provisions shall be provided at the island or peninsula for future addition of a receptacle outlet to serve the island or peninsular countertop or work surface.

(3) Receptacle Outlet Location.

Receptacle outlets shall be located in one or more of the following:

  • (1) On or above, but not more than 500 mm (20 in.) above, a countertop or work surface.
  • (2) In a countertop using receptacle outlet assemblies listed for use in countertops.
  • (3) In a work surface using receptacle outlet assemblies listed for use in work surfaces or listed for use in countertops.
  • This revised section does not go into effect until 12/31/2026.

Till next time be safe work safe.

Jake

Continue Reading210.52©(2) Island and Peninsular Countertops and Work Surfaces, (3) Receptacle Outlet Location.

210.8(F) Outdoor Outlets. Exceptions #2

The temporary exception that delayed GFCI protection for outdoor HVAC equipment at dwelling units is about to expire. Several TIAs have been submitted to NFPA and will be reviewed in September, and some may extend the exception. Until any extension is officially approved, Florida contractors must install GFCI protection on all outdoor HVAC equipment at residential dwellings.

We’ll continue to monitor NFPA action and provide updates as soon as new information is released. At this time, HVAC and GFCI manufacturers are still working to produce devices that operate reliably together, so please plan installations accordingl

I have the TIA’s below for you to read.

 image

image

image

image

image

image

Continue Reading210.8(F) Outdoor Outlets. Exceptions #2

210.12 Arc-Fault Circuit-Interrupter Protection (D) Other Occupancies.

The 2023 code has expanded the commercial areas that require Arc‑Fault Circuit‑Interrupter (AFCI) protection. Sleeping areas in fire stations, police stations, and similar facilities are now required to have AFCI protection. If you’re unsure whether your installation falls under these requirements, contact your local inspector.

image

Until next time, stay safe out there and work safe.

Jake

Continue Reading210.12 Arc-Fault Circuit-Interrupter Protection (D) Other Occupancies.

Garage Branch Circuits 210.11(C)

This update isn’t actually a change but a clarification of what the section requires. You must install at least one 20‑ampere circuit to serve garage receptacles. Any additional circuits you choose to install do not have to be 20-amperes — they may be 15‑ampere circuits. So if you’re adding a refrigerator, central vacuum, or  equipment, those additional receptacle circuits can be 15 amperes rather than 20.

image

Bes safe work safe.

Jake

Continue ReadingGarage Branch Circuits 210.11(C)

Receptacles on a Dock 555.33

New to Article 555 is new to Receptacle replacement. This section applies if you are replacing receptacle outlets on a dock. 555.33(C) states that they need to be at least 12” above the dock but not below the electrical datum plane on a fixed dock.

image


PICTURE OF THE WEEK, TRYING TO KEEP THINGS COOL!!!! BUT THE BREAKER KEEPS TRIPPING.

Thanks Scott!!

FAN

Till next time be safe work safe.

Jake

Continue ReadingReceptacles on a Dock 555.33

555.3 Electrical Datum Plan Distances

This weeks change addresses docks and the datum plane for mounting equipment on a dock.

image

Throughout Article 555, the physical location of electrical equipment is referenced to the electrical datum plane, which is used as a horizontal benchmark on land and on floating piers. The definition of the term electrical datum plane encompasses areas subject to tidal movement and areas in which the water level is affected only by conditions such as climate (rain or snowfall) or by human intervention (the opening or closing of dams and floodgates). In either case, the term covers the normal highest water level, such as astronomical high tides. The term does not cover extremes due to natural or manmade disasters.

Till next time be safe work safe.

Jake



Continue Reading555.3 Electrical Datum Plan Distances

430.7 Markings on MOTOR NAMEPLATES 2020 NEC

New to this section is requirement #16 for motors that are electronically protected to be marked on the nameplate. 

Got a great picture this week from George in West Palm beach, thanks George great picture.  See below.

If you want to make the pictures bigger just click on them.

Electronically protected motors

Not sure what you call it but I would say a raceway “SPLITTER”!!!

SPLITTER

Should try and get this fitting listed.

Till next time be safe work safe.

Jake

Continue Reading430.7 Markings on MOTOR NAMEPLATES 2020 NEC

410.118 Access to other boxes.

This new section does away with pulling down a fixture in a drywall or hard ceiling to access a junction box above the ceiling.  It now requires the box to be part of the fixture when it’s above a drywall or hard ceiling.

410.118

I don’t know who sent the picture of the week, but WOW!!!  Look it over tell me what you think.

IMG-20240307-WA0000

Till next time be safe work safe.

Jake

Continue Reading410.118 Access to other boxes.