HOW TO SIZE A RESIDENTIAL SERVICE PER SECTION 310.15(B)(7), USING THE 83% RULE

  • Post author:
  • Post category:News

Screenshot 2023-02-19 121040

Sizing of Service and/or Feeder Conductors for a dwelling unit PER SECTION 310.15(B)(7) see Example D7 in ANNEX D in the back of the Code book.

Service conductors and feeders for certain dwellings are permitted to be sized in accordance with 310.15(B)(7).

If a 200-ampere service is required, to select the service conductor size is as follows:

200 amperes (the size of required main) × 0.83 = 166 amperes per 310.15(B)(7).  (THIS IS THE 83% RULE)

If no other adjustments or corrections are required for the installation, then, in accordance with Table 310.15(B)(16), a 2/0 AWG Cu which is good for 175 amperes or a 4/0 AWG Al  which is good for 180 amperes will meet this rating at 75°C (167°F).

The following is the section from the 2017 Code book.

310.15(B)(7) Single-Phase Dwelling Services and Feeders.

For one-family dwellings and the individual dwelling units of two-family and multifamily dwellings, service and feeder conductors supplied by a single-phase, 120/240-volt system shall be permitted to be sized in accordance with 310.15(B)(7)(1) through (4).

As you can see this section it is for “one and two family dwellings, and multifamily dwellings”that use 120/240 voltages for services and/or feeders. In this section a reduced neutral is allowed.


For one-family dwellings and the individual dwelling units of two-family and multifamily dwellings, single-phase feeder conductors consisting of 2 ungrounded conductors and the neutral conductor from a 208Y/120 volt system shall be permitted to be sized in accordance with 310.15(B)(7)(1) through (3).

In this section we can use it for the same types of units, but the voltage is 208Y/120 and a reduced neutral “can not be used”.  So you will be required to pull the same size neutral under this section.    Here in South Florida this voltage is used in Multifamily buildings.



(1) For a service rated 100 through 400 amperes, the service conductors supplying the entire load associated with a one-family dwelling, or the service conductors supplying the entire load associated with an individual dwelling unit in a two-family or multifamily dwelling, shall be permitted to have an ampacity not less than 83 percent of the service rating.

(2) For a feeder rated 100 through 400 amperes, the feeder conductors supplying the entire load associated with a one-family dwelling, or the feeder conductors supplying the entire load associated with an individual dwelling unit in a two-family or multifamily dwelling, shall be permitted to have an ampacity not less than 83 percent of the feeder rating.

(3) In no case shall a feeder for an individual dwelling unit be required to have an ampacity greater than that specified in 310.15(B)(7)(1) or (2).

(4) Grounded conductors shall be permitted to be sized smaller than the ungrounded conductors, if the requirements of 220.61 and 230.42 for service conductors or the requirements of 215.2 and 220.61 for feeder conductors are met.


The table below comes from ANNEX D in the back of the 2017 CODE book.

This table was made using the 83% rule for sizing the conductors to a residential dwelling unit.

Coming in the 2020 Code Book this Table will have a home at 310.12 which will be nice to see it back in the Code book where it belongs.  The inclusion of the 83% rule confused many people and was mis-interpreted all the time.  I was often asked if it was 83% of the load calculation, 83% of the wire size and a number of other mis-understood interpretations.



Screenshot 2023-02-19 111943

One of the most important parts of this 83% rule is that the load calculation can exceed the ampacity of the conductors chosen.

An example is a 200a load calculation comes out to 190 amperes.  We are allowed to use the 83% rule because it is a residential service or feeder.  The 200 ampere service rating is multiplied by the 83% ( 200  X 83%  =  166. amperes) which gives us 166 amperes.  We then go to Table 310.15(B)(16) and go down the 75 degree column and find the a 2/0 copper conductor has the ampacity of 175 amperes which exceeds the 166 ampere used in the 83% rule, so a 2/0 Cu. can be used for a 200 ampere service or feeder.

Hope this helps.

Till next time be safe work safe.

Jake


Continue ReadingHOW TO SIZE A RESIDENTIAL SERVICE PER SECTION 310.15(B)(7), USING THE 83% RULE

210.52(G)(1) Basement, Garages, and Accessory Buildings Exception. “DO NOT USE UNTIL 12.31.23”

This is a new exception to this required outlet in garages.  If you are wiring an apartment building that has separate garages for some of the units it is not required to have an outlet in that space.

image

Till next time, Be safe work safe

Jake

Continue Reading210.52(G)(1) Basement, Garages, and Accessory Buildings Exception. “DO NOT USE UNTIL 12.31.23”

210.52(C)(2) Island and Peninsular Countertops and Work Surfaces 2020 Code Change (12/31/23 in Florida)

New for the 2020 Code is a big change to Islands and peninsulas and work surfaces.  You will have to calculate the square footage of the surface and figure out how many receptacle outlets are needed.  The first 9 sq. ft or less gets one and then and additional one for every 18 sq. ft or faction thereof.  Then looking at part (b) at least one outlet shall be located within 2 ft. of the outer end of a peninsular or work surface, and the rest being located per the installer, designer, or building owner.

We would like to wish all of you a Very Merry Christmas and a Happy New Year!  

image

Till Next Year be safe, party safe, and work safe.

Jake

Continue Reading210.52(C)(2) Island and Peninsular Countertops and Work Surfaces 2020 Code Change (12/31/23 in Florida)

210.12 Arc-Fault Circuit-Interrupter Protection. NOT TO BE USED UNTIL 12/31/23

New to section 210.12 for Arc Fault circuits are added locations.  Patient Sleeping Rooms in Nursing Homes and Limited-Care Facilities are protected areas new to this section.

210.12 (C) Guest Rooms, Guest Suites, and Patient Sleeping Rooms in Nursing Homes and Limited-Care Facilities.

All 120-volt, single-phase, 15- and 20-ampere branch circuits supplying outlets and devices installed in guest rooms and guest suites of hotels and motels and patient sleeping rooms in nursing homes and limited-care facilities shall be protected by any of the means described in 210.12(A)(1) through (6).


210.12C

Each new Code cycle we get a little more Arc Fault protection.  Some day it will all be Arc Fault protected.  Which isn’t a bad thing.

Well that’s all for this week, have a safe and happy Thanksgiving.

Jake


Continue Reading210.12 Arc-Fault Circuit-Interrupter Protection. NOT TO BE USED UNTIL 12/31/23

210.8 Ground-Fault Circuit-Interrupter Protection for Personnel. 210.8(B) Other Than Dwelling Units. COMMERCIAL AREAS NOT TO BE USED UNTIL 12/31/23

New to 2020 NEC is more areas in commercial and industrial areas that GFCI protection is needed.

Screenshot 2022-11-06 150614

Till next time be safe work safe

Jake

Continue Reading210.8 Ground-Fault Circuit-Interrupter Protection for Personnel. 210.8(B) Other Than Dwelling Units. COMMERCIAL AREAS NOT TO BE USED UNTIL 12/31/23

210.8 GFCI protection for personnel 210.8(A)(11) Indoor damp and wet locations. NOT TO BE USED UNTIL 12/31/23

A new part was added to residential GFCI protection for the 2020 Code,  indoor damp and wet locations.  This could be the breeze way leading in from your pool or a mud room leading in from the back door.

image

Till next time be safe work safe.

Jake

Continue Reading210.8 GFCI protection for personnel 210.8(A)(11) Indoor damp and wet locations. NOT TO BE USED UNTIL 12/31/23

2020 Code change for GFCI protection. NOT TO BE USED UNTIL 12/31/23

New to section 210.8 GFCI protection is the inclusion of up to 250v receptacle outlet both for residential and commercials installations.They will be required in all the locations shown in 210.8(A) and (B) below.

210.8 (A) Dwelling Units.

All 125-volt through 250-volt receptacles installed in the locations specified in 210.8(A)(1) through (A)⁠(11) and supplied by single-phase branch circuits rated 150 volts or less to ground shall have ground-fault circuit-interrupter protection for personnel.

(1) Bathrooms

(2) Garages and also accessory buildings that have a floor located at or below grade level not intended as habitable rooms and limited to storage areas, work areas, and areas of similar use

(3) Outdoors                                                                                                                                                                                                                                                                             

Exception to (3) Receptacles that are not readily accessible and are supplied by a branch circuit dedicated to electric snow-melting, deicing, or pipeline and vessel heating equipment shall be permitted to be instal⁠led in accordance with 426.28 or 427.22, as applicable.

(4) Crawl spaces — at or below grade level

(5) Basements                                                                                                                                                                                                                                                                           

Exception to (5): A receptacle supplying only a permanently installed fire alarm or burglar alarm system shall not be required to have ground-fault circuit-interrupter protection.        Informational Note: See 760.41(B) and 760.121(B) for power supply requirements for fire alarm systems. Receptacles installed under the exception to 210.8(A)⁠(5) shall not be considered as meeting the requirements of 210.52(G).

(6) Kitchens — where the receptacles are installed to serve the countertop surfaces

(7) Sinks — where receptacles are installed within 1.8 m (6 ft) from the top inside edge of the bowl of the sink

(8) Boathouses

(9) Bathtubs or shower stalls — where receptacles are instal⁠led within 1.8 m (6 ft) of the outside edge of the bathtub or shower stall

(10) Laundry areas                                                                                                                                                                                                                                                                  

Exception to (1) through (3), (5) through (8), and (10):                                                                                                                                                                                                                  Listed locking support and mounting receptacles utilized in combination with compatible attachment fittings installed for the purpose of serving a ceiling luminaire or ceiling fan shall not be required to be ground-fault circuit-interrupter protected. If a general-purpose convenience receptacle is integral to the ceiling luminaire or ceiling fan, GFCI protection shall be provided.

(11) Indoor damp and wet locations

(B) Other Than Dwelling Units.

All 125-volt through 250-volt receptacles supplied by single-phase branch circuits rated 150 volts or less to ground, 50 amperes or less, and all receptacles supplied by three-phase branch circuits rated 150 volts or less to ground, 100 amperes or less, installed in the locations specified in 210.8(B)(1) through (B)(12) shall have ground-fault circuit-interrupter protection for personnel.

(1) Bathrooms

(2) Kitchens or areas with a sink and permanent provisions for either food preparation or cooking

(3) Rooftops                                                                                                                                                                                                                                                                                    

Exception: Receptacles on rooftops shall not be required to be readily accessible other than from the rooftop.

(4) Outdoors                                                                                                                                                                                                                                                                        

Exception No. 1 to (3) and (4): Receptacles that are not readily accessible and are supplied by a branch circuit dedicated to electric snow-melting, deicing, or pipeline and vessel heating equipment shall be permitted to be installed in accordance with 426.28 or 427.22, as applicable.

Exception No. 2 to (4): In industrial establishments only, where the conditions of maintenance and supervision ensure that only qualified personnel are involved, an assured equipment grounding conductor program as specified in 590.6(B)(2) shall be permitted for only those receptacle outlets used to supply equipment that would create a greater hazard if power is interrupted or having a design that is not compatible with GFCI protection.

(5) Sinks — where receptacles are installed within 1.8 m (6 ft) from the top inside edge of the bowl of the sink

Exception No. 1 to (5): In industrial laboratories, receptacles used to supply equipment where removal of power would introduce a greater hazard shall be permitted to be installed without GFCI protection.

Exception No. 2 to (5): Receptacles located in patient bed locations of Category 2 (general care) or Category 1 (critical care) spaces of health care facilities shall be permitted to comply with 517.21.

(6) Indoor damp and wet locations

(7) Locker rooms with associated showering facilities

(8) Garages, accessory buildings, service bays, and similar areas other than vehicle exhibition halls and showrooms

(9) Crawl spaces — at or below grade level

(10) Unfinished areas of basements

Exception to (1) through (5), (8), and (10): Listed locking support and mounting receptacles utilized in combination with compatible attachment fittings installed for the purpose of serving a ceiling luminaire or ceiling fan shall not be required to be ground-fault circuit-interrupter protected. If a general-purpose convenience receptacle is integral to the ceiling luminaire or ceiling fan, GFCI protection shall be provided.

(11) Laundry areas

(12) Bathtubs and shower stalls — where receptacles are installed within 1.8 m (6 ft) of the outside edge of the bathtub or shower stall

CAN’T SEE THE PICTURE CLICK ON THE LINK.

image

Till next time be safe work safe

Jake

Continue Reading2020 Code change for GFCI protection. NOT TO BE USED UNTIL 12/31/23

210.8 Ground-Fault Circuit-Interrupter Protection for Personnel.

This weeks post has a change that will affect a few installations.  The garbage disposal will now have to be GFCI protected because they took out the words door and doorway in the section when measuring the distance from a sink.  It will also effect the outlets in hallways that are close to the bathroom, so you will have to position your outlets strategically when you have outlets in the hallway near a bathroom sink in order to save a little money.

Again these are not in use at this time they will be adopted on 12/31/2023.

image

I also received a couple of great pictures from Nancy, thanks for the great pictures.  I never “wood” have never thought of using them this way.

clip_image001[4]

clip_image001

Till next time be safe work safe

Jake

Continue Reading210.8 Ground-Fault Circuit-Interrupter Protection for Personnel.