Identifying neutral conductors grouped in a panelboard or enclosure

   This weeks 2014 Code change comes from section 200.4(B) which deals with neutrals grouped in panelboards or enclosures.  Then identifying them so that you don’t mistakenly disconnect the wrong one and send an over or under voltage  to a piece of equipment and possibly burn it up.  This section requires us to identify the neutral conductor for each circuit or circuits it serves.  This is for single circuit or multi-wire circuit. 

   Over the years I have seen electricians working on circuits only to disconnect the neutral to move it around to make room for another neutral conductor, only to disconnect it while the circuit it serves was still energized.  This resulted in a burnt out refrigerator or computer that was on a multi-wire circuit.

   I have seen a few good ways to ID the neutrals by either numbering them with the corresponding circuit number(s) on each neutral or grouping them with a piece of the sheath from NM cable marked with the circuit ID. 

   There are a couple of Exceptions where you can tell which neutral goes with a particular circuit of a cable or conduit installation, or when there just isn’t room to mark the wire in an existing installation where the conductors are pulled through a box or enclosure without splices.

 image

Till next time work safe be safe and keep an eye on your helper.

Jake

Continue ReadingIdentifying neutral conductors grouped in a panelboard or enclosure

Low Voltage lights around a pool

This question has come up several times in the last couple of weeks. How close can I put my low voltage lights near a pool?

Section 680.22,B6 allows us to install LV fixtures closer than 5’ but they have to meet 680.23, A 2  for the type of transformer that is allowed to feed the fixtures.

680.22 B(6) Low-Voltage Luminaires. Listed low-voltage luminaires not requiring grounding, not exceeding the low-voltage contact limit, and supplied by listed transformers or  power supplies that comply with 680.23(A)(2) shall be permitted to be located less than 1.5 m (5 ft.) from the inside walls of the pool.

(2) Transformers and Power Supplies. Transformers and power supplies used for the supply of underwater luminaires, together with the transformer or power supply enclosure, shall be listed for swimming pool and spa use. The transformer or power supply shall incorporate either a transformer of the isolated winding type, with an ungrounded secondary that has a grounded metal barrier between the primary and secondary windings, or one that incorporates an approved system of double insulation between the primary and secondary windings.

LV fixtures at pool

Till next time

Be safe, work safe

Jake

Continue ReadingLow Voltage lights around a pool

Florida Building Code Residential Electrical Code

  • Post author:
  • Post category:News
  • Post comments:0 Comments

This weeks post comes from the Florida Building Code Residential Electrical code from Chapters 34 through 45.  Inside each chapter they have given us some of the best illustrations that I’ve seen. So every now and then I will pull up one or two to show you.  This one shows the clearances from overhead services to platforms , widows and  the like.  A good illustration on what the code implies (230.9).

Service clearances

Till next time be safe work safe

Jake

Continue ReadingFlorida Building Code Residential Electrical Code

2014 Code Change 250.68 (C)(2)

  • Post author:
  • Post category:News
  • Post comments:0 Comments

This weeks change allows us to use the steel frame of a building in place of running a conductor all around a building.   Bonding each item that needs to be bonded into part of the Grounding Electrode system.  Such as the case of the electrical service on one side of the building and the cold water service on the other.

.250.68 C 2

Till next time be safe work safe

Jake

Continue Reading2014 Code Change 250.68 (C)(2)

2014 Code Change 250.68(C)(3) Grounding Electrode Connection

  • Post author:
  • Post category:News
  • Post comments:0 Comments

image

In the 2014 NEC they are going to allow us to extend the connection from Grounding Electrode (concrete encased electrode)

into a wall or above grade. In the past we could only have the conductor from the rebar extending out from the concrete

encasement, now we can have the rebar extend out from the encasement for a connection.  So this will work when the

town or city will not let you make this connection in the meter can, and you have a main breakers panel as your first means

of disconnect, you bond the neutral to this electrode in the wall near the panel if needed.  As you can see in the picture on the

right the connection has to be accessible.

 

Till next time be safe work safe.

 

Jake

Continue Reading2014 Code Change 250.68(C)(3) Grounding Electrode Connection