Single Phase dwelling services

It’s back, after a few years they finally brought this table back into the Code.  For the last few cycles it has been found in the examples back in Annex D.  It’s been a few years but it’s back  The 83% still lives on, but they also gave us 31012 TABLE, which shows us what size conductors we can use for a dwelling service.  Remember this TABLE only works when we feed the entire load from one feeder/service (see A through D below).  If you have two mains then this table does not work and you have to go to 310.16 for the conductors.

image

A through D below applies to 120/240 single phase services, and A through C applies to 120/208Y services.

(A) Services.  For a service rated 100 amperes through 400 amperes, the service conductors supplying the entire load associated with a one-family dwelling, or the service conductors supplying the entire load associated with an individual dwelling unit in a two-family or multifamily dwelling, shall be permitted to have an ampacity not less than 83 percent of the service rating. If no adjustment or correction factors are required, Table 310.12 shall be permitted to be applied.

(B) Feeders.  For a feeder rated 100 amperes through 400 amperes, the feeder conductors supplying the entire load associated with a one-family dwelling, or the feeder conductors supplying the entire load associated with an individual dwelling unit in a two-family or multifamily dwelling, shall be permitted to have an ampacity not less than 83 percent of the feeder rating. If no adjustment or correction factors are required, Table 310.12 shall be permitted to be applied.

(C) Feeder Ampacities.  In no case shall a feeder for an individual dwelling unit be required to have an ampacity greater than that specified in 310.12(A) or (B).

(D) Grounded Conductors.  Grounded conductors shall be permitted to be sized smaller than the ungrounded conductors, if the requirements of 220.61 and 230.42 for service conductors or the requirements of 215.2 and 220.61 for feeder conductors are met.

Where correction or adjustment factors are required by 310.15(B) or (C), they shall be permitted to be applied to the ampacity associated with the temperature rating of the conductor.

Informational Note No. 1:

The service or feeder ratings addressed by this section are based on the standard ampere ratings for fuses and inverse time circuit breakers from 240.6(A).

image

Till next time be safe work safe.

Jake