Code changes that will affect the results of your inspection or plan review.

  • Post author:
  • Post category:News
  • Post comments:0 Comments

In sections 110.24 (A)(B) the Code has made it your job to verify the available fault current at the service.  You will need to field mark the equipment with the fault current that is available at your service and with the date the calculation was performed.  These markings need to be legible and able to withstand the environmental conditions of our South Florida climate; sunlight and water resistant.

The available fault current will be calculated on the basis of a number of contributing factors like the size of the utility transformer and the location of the transformer in proximity to your service.  The type, length, and size of conductors used in your service will also figure into the available fault current.  Not marking your service will delay receiving a final inspection from your local inspector or issuance of your permit from your plans examiner. The 2011 Code goes into effect on July 1st .  All plans and permits received after this date will be governed by these new changes. I am bringing these changes to your attention so it wont be a surprise when the AHJ asks.

When you sit down to figure the price for that next service change or modification, remember that in order to perform these calculations you will need information that is not readily available to you. You will need to contact the utility for some of this information.  This will cost you time; and we all know time costs you money.

 

Fault Current

Continue ReadingCode changes that will affect the results of your inspection or plan review.

210.12 (B)(1,2) 2011 NEC New Branch Circuit requirements.

  • Post author:
  • Post category:News
  • Post comments:0 Comments

This new Code change will go into affect on July 1, 2015. 

Under this new change it states that when you modify, replace, or extend branch circuit wiring it will have to be protected by one of the following devices.

(1) A listed combination type AFCI located at the origin of the branch circuit.

(2) A listed outlet branch circuit type AFCI located at the first receptacle outlet of the existing branch circuit.

So be aware that this will be enforced and you will need to comply in order to pass your electrical inspection.

 

I will try to send out more of the significant changes in the next few weeks to bring you up to date with the ever changing way we do our jobs.  

If you have any question please email me at jleccemail@hotmail.com

 

Thanks and be careful out there.

Jake

Continue Reading210.12 (B)(1,2) 2011 NEC New Branch Circuit requirements.

2011 NEC adoption

  • Post author:
  • Post category:News
  • Post comments:0 Comments

For the third time I am sending out an email that is informing you that the 2011 NEC will be adopted on different date than the last posting.

JULY 1, 2015 is the new date for adoption and hopefully the last.

 

Jake

Continue Reading2011 NEC adoption

NEW FLORIDA STATUTE FOR SMOKE ALARMS

  • Post author:
  • Post category:News
  • Post comments:0 Comments

553.883 Smoke alarms in one-family and two-family dwellings and townhomes.—One-family and two-family dwellings and townhomes undergoing a repair, or a level 1 alteration as defined in the Florida Building Code, may use smoke alarms powered by 10-year nonremovable, nonreplaceable batteries in lieu of retrofitting such dwelling with smoke alarms powered by the dwelling’s electrical system. Effective January 1, 2015, a battery-powered smoke alarm that is newly installed or replaces an existing battery-powered smoke alarm must be powered by a nonremovable, nonreplaceable battery that powers the alarm for at least 10 years. The battery requirements of this section do not apply to a fire alarm, smoke detector, smoke alarm, or ancillary component that is electronically connected as a part of a centrally monitored or supervised alarm system.

History.—s. 25, ch. 2014-154.

 

Make sure that you check with the local authority.  They may have more stringent rules that apply.

Continue ReadingNEW FLORIDA STATUTE FOR SMOKE ALARMS

UL search tool

  • Post author:
  • Post category:News
  • Post comments:0 Comments

I was sent this search tool from UL and wanted to share it with you.  Just click on the link and then click on the appropriate book you want to search.

I have tried several 2011 Code book searches and they all helped me find what I was looking for!  This tool will help you search listings for different materials

and how they are listed.  Let me know what you think!  Found it to be a great help when a listing question comes up.

 

http://codelink.ul.com 

 

Till the next time work safe be safe.

 

Jake

Continue ReadingUL search tool

Available Fault Current

In the 2011 NEC article 110.24 has a few changes that need to be be addressed.  Under 110.24(A) Field Marking, service equipment in other than a dwelling unit shall be field marked with the maximum available fault current.  This is something you will have to get with the utility or the engineer for the project to be able to calculate.  The field markings will have to be able to with stand the elements when a attached to a disconnect or panelboard out in the field.   Section 110.24(B) Modifications will make you as the installer responsible to attach newly calculated fault current information to the equipment based on modification made to the circuits.  All information provided will have to with stand the elements in which they are installed so a Sharpie or Magic Marker is not going to meet the requirements of this new change because they don’t last out in the weather.   Till next time work safe…

 

image

Continue ReadingAvailable Fault Current

Panelboard identification 408.4(B)

For the 2011 edition of the NEC on page 275 of the softbound Code book, they have added the requirement for field identification of all switchboards and panelboards, to indicate where the power to that equipment originates.  It will be easier to mark these panel and switch boards when they are installed.  Trying to find the source 5 or 10 years down the road has always been a time consuming project that only takes minutes when first installed.  A great addition to the code, will make life as an electrician easier in the future.  Till next time work safe and be safe.

 

Jake

Continue ReadingPanelboard identification 408.4(B)